Natural Gas vs Propane for a Home Standby Generator
Propane gives slightly more power (Generac's 22 kW unit is rated 22 kW on propane vs 21 kW on natural gas) and works anywhere a tank can go. Natural gas never needs refilling and is usually cheaper to run, but requires a utility gas line with enough capacity.
The short answer
Choose natural gas if your home already has a gas service that can supply the generator’s full-load demand. You’ll never refill a tank, it won’t go stale, and running costs are usually lower. Choose propane if there’s no gas line, if you want fuel stored on your own property, or if you need every last watt of rated output. Both are clean-burning gaseous fuels that most standby generators can use.
Power: propane wins slightly
Manufacturers rate standby generators higher on propane. From their specification pages:
| Generator | Rated on propane | Rated on natural gas | Difference |
|---|---|---|---|
| Generac Guardian 22 kW (7042) | 22,000 W | 21,000 W | −5% |
| Kohler 20RCAL | 20,000 W | 18,000 W | −10% |
The reason is energy content. EIA lists a cubic foot of natural gas at about 1,036 Btu. Propane vapor is denser in energy — Generac’s fuel guidance uses about 2,500 Btu per cubic foot of propane vapor. The engine’s intake can only draw so much volume per cycle, so it makes a little less power on natural gas. Size your generator using the rating for the fuel you’ll actually use; our generator size calculator lets you pick the fuel.
Fuel use: similar energy, different units
At half load, Generac lists the 22 kW Guardian at 221 cubic feet per hour of natural gas or 2.53 gallons per hour of propane. Converted with EIA’s heat-content figures (1,036 Btu per cubic foot of natural gas; 91,452 Btu per gallon of propane):
- Natural gas: 221 × 1,036 ≈ 229,000 Btu per hour
- Propane: 2.53 × 91,452 ≈ 231,000 Btu per hour
In other words, the engine burns about the same energy either way. The cost difference comes from what you pay per Btu, not from efficiency.
Cost per hour
- Propane: 2.53 gal/h × EIA’s U.S. average residential price for the week of November 23, 2026 ($2.813/gal) ≈ $7.12 per hour. State averages ranged from $1.79 to $5.16 a gallon among surveyed states, so your figure could be much lower or higher.
- Natural gas: 221 ft³/h ≈ 2.29 therms per hour. Multiply by the all-in rate per therm on your gas bill.
Run your own numbers in the generator running cost calculator, or see daily propane costs by state.
Runtime and supply
Natural gas comes from the utility, so runtime is effectively unlimited in a typical power outage. Gas distribution generally keeps working when the electric grid fails, although it can be interrupted by earthquakes, floods or pipeline problems. The catch is capacity: the meter, service line and house piping must deliver the generator’s full-load flow while the furnace and water heater also run. Generac’s guidance notes that fuel pipes must be sized for full load. Your installer may need the gas utility to upgrade the meter.
Propane is stored on site, so you control the supply — and the risk of running out. A full 500-gallon tank holds about 400 gallons, enough for about 6.6 days at half load on the 22 kW unit. Deliveries may be delayed during widespread storms, so most owners keep the tank topped up before hurricane or winter-storm season. Check runtime for your tank with the propane runtime calculator.
Installation differences
- Natural gas: a gas line from the meter to the generator, possibly a larger meter or regulator. Typically less equipment on the property.
- Propane: a tank — often 250 to 1,000 gallons for whole-house standby — with setbacks from buildings and property lines set by code and your supplier, plus the line to the generator. Tanks can be bought or leased.
- Both: a concrete or composite pad, a transfer switch, electrical permits and inspection. Kohler and Generac both publish installation requirements for clearances and fuel pressure.
Decision checklist
- Do you have natural gas service? If not, propane (or a large portable on gasoline) is your option.
- Can the gas service supply full load plus your other gas appliances? If not, budget for upgrades or consider propane.
- How long are your outages? For multi-day outages without natural gas, size the propane tank for at least the longest outage you expect, plus a margin.
- How much power do you need? If your load is close to the generator’s natural gas rating, the propane rating or the next size up gives headroom.
- What does fuel cost where you live? Compare cost per hour using your actual gas rate and propane price.
Whatever you choose, the generator must be installed outdoors with the manufacturer’s clearances, and the connection to your home should be made by licensed professionals.
Common misconceptions
- “Propane is always more expensive.” Not necessarily. Prices vary widely by state and season, and natural gas rates vary by utility. Compare cost per hour at your actual prices.
- “Natural gas never fails.” It is very reliable during electrical outages, but not guaranteed after major earthquakes, floods or supply emergencies.
- “Bigger tank, bigger generator.” Tank size sets runtime, not power. Power comes from the generator’s rating on the fuel you use.
Frequently asked questions
Why does a generator make less power on natural gas?
Natural gas carries less energy per cubic foot than propane vapor, so the same engine takes in less energy per cycle. Manufacturers rate their units lower on natural gas — for example 21 kW vs 22 kW for Generac's 22 kW Guardian and 18 kW vs 20 kW for Kohler's 20RCAL.
Can I switch a standby generator between natural gas and propane?
Most air-cooled standby units are field-convertible between the two, but the conversion is done by an installer and the fuel supply, regulator and line sizing must match. It isn't a switch you flip during an outage.
How big a propane tank do I need for a standby generator?
It depends on how many days you want to cover. A 500-gallon tank (about 400 gallons usable) runs a 22 kW unit at half load for about 6.6 days. Check your supplier's minimum tank size for the generator.
Is my gas meter big enough for a generator?
Not always. A 22 kW generator can burn over 300 cubic feet per hour at full load, on top of your furnace and water heater. Your installer and gas utility should confirm the meter and line can supply the total.
Which fuel is cheaper to run?
Compare cost per hour. At half load the Generac 22 kW burns 221 ft³/h of natural gas (about 2.29 therms) or 2.53 gal/h of propane. Multiply by your gas rate per therm and your propane price per gallon. Use our running cost calculator.
Sources
- Generac — 22kW Standby Generator (7042) specifications (accessed 2026-11-25)
- Generac — How Much Fuel Does My Home Standby Generator Use (accessed 2026-11-25)
- Kohler Home Energy — 20RCAL specifications (accessed 2026-11-25)
- U.S. Energy Information Administration — Units and calculators explained (heat content) (accessed 2026-11-25)